Product Code : 31
Features
Technical Data
Item / Model
NV-400
Detection Principle
Hot Air Semiconducter
Gas Detected
NV-400 : Town gas (Natural gas)
Detection Points per Unit
Monitors 2 points per unit
Detection Range
NV-400 : 0-100%LEL
Concentration IndicatorAlarm Set Value IndicationBacklightPeak Hold Function (on alarm)
LCD bar-graph meter (53 dots x 2 lines)Direct reading scaleYesHolds a peak value on alarm, which is canceled by the reset
Alarm Set Value (default value)
NV-400: 10%LEL fir Ist stage, 24%LEL for 2nd stage
Alarm Accuracy
ñ25% of an Alarm Set Value (under identical conditions)
Response Time
NV-400: 30s or less at 160% concentration of an Alarm Set Value (excluding sampling delay for suction type)
Alarm Indication
Individual Alarm LampSelf-holding type
On Alarm : Flashes red, lights up after the Buzzer Stop Complete lock (Turn off by the reset after the level declined)
Alarm Sound
On Alarm : Intermittent buzzer, stops after the Buzzer Stop
External Alarm Output
Individual Alarm Contact
1 a no-voltage (Contact capacity : 2A@100V AC)
Individual Voltage output
0-6-12V DC (20,A or Less)
Collective Alarm Contact
1 c no-voltage (Contact capacity : 2A@100V AC)
Centralized Monitor Panel Output
External Buzzer Contact
External Buzzer Voltage Output
Intermittent voltage signal (12V DC, 10mA or less)
Alarm Delay
Selectable by a DIP awitch (10s constant)
Main power Source
85-264V AC
Power Consumption
When Using KD-5
Diffusion type (15+3.5n)VA
When Using PE-2DC
Suction type (15+7.5n)VA
Backup Power Source (Only on models with a built-in backup power supply)
Battery Type
Sealed Lead Acid Battery
Overdischarge Prevention Function
Yes
Battery Life Check Function
Battery Viltage indication
2-digit LED
exterior Color
Munsell 2.5PB 7.0/1.0